PPD512控制器
通信端口后面板上的RS-232端口使用DB-9母連接器。圖4-4說明了引腳通信端口的分配,以及表4-4確定了RS-232連接器引腳
功能。標(biāo)準(zhǔn)通信電纜使用DB-9公連接器端接
對(duì)于與DECS-100的PC接口,如所示
圖4-5典型應(yīng)用的DECS-100連接
圖4-6至圖4-10說明了使用DECS-100的典型應(yīng)用DECS-100操作功率來自永磁發(fā)電機(jī)(PMG)的應(yīng)用,以及DECS-100采用三相電壓傳感。圖4-7顯示了另一種PMG應(yīng)用,但具有單相電壓感測(cè)。圖4-8顯示了DECS-100操作功率為從發(fā)電機(jī)輸出(并聯(lián)應(yīng)用)導(dǎo)出,三相電壓感應(yīng)應(yīng)用于DECS-100。圖4-9顯示了另一種分流應(yīng)用,但具有單相傳感。圖4-10顯示DECS-100由三相傳感應(yīng)用中的單相電站電源供電。
圖4-11顯示了在交叉電流中運(yùn)行的兩臺(tái)并聯(lián)發(fā)電機(jī)的典型連接圖補(bǔ)償(無功差動(dòng))模式。所示電阻器的值為0.1歐姆。這是典型的可用于設(shè)置負(fù)擔(dān)的值。(確保電阻器的額定功率足以滿足安裝。)以下段落描述了CE(歐洲)的安裝和布線要求社區(qū))兼容安裝。
安裝DECS-100必須安裝在接地的金屬外殼(導(dǎo)管箱)內(nèi)。檢修面板應(yīng)覆蓋前面板顯示器的開口。
裝電線與下列端子連接的接線必須屏蔽。每個(gè)屏蔽應(yīng)終止于:在導(dǎo)管箱外部接地。
?電流感應(yīng)端子CT1和CT2
?繼電器輸出端子AL1和AL2
?無功/功率因數(shù)控制觸點(diǎn)輸入端子52J和52K
?并聯(lián)發(fā)電機(jī)補(bǔ)償端子52L和52M
?升高和降低觸點(diǎn)輸入端子6U、6D和7
?附件輸入電壓端子A和B
?電壓匹配觸點(diǎn)輸入端子VM和VMC
1。標(biāo)記并斷開DECS-100的所有接線。確保絕緣接線端子,以防止短路。
2.啟動(dòng)原動(dòng)機(jī)并執(zhí)行所有發(fā)動(dòng)機(jī)調(diào)速器調(diào)整。
3.完成所有初始調(diào)速器調(diào)整后,關(guān)閉原動(dòng)機(jī)。
Communication Port
The RS-232 port on the rear panel uses a DB-9
female connector. Figure 4-4 Illustrates the pin
assignments of the communication port and
Table 4-4 Identifies the RS-232 connector pin
functions. A standard communication cable
terminated with a DB-9 male connector is used
for PC interface with the DECS-100 as shown in
Figure 4-5. DECS-100 Connections for Typical Applications
Figures 4-6 through 4-10 illustrate typical applications using the DECS-100. Figure 4-6 shows an
application where DECS-100 operating power is derived from a permanent magnet generator (PMG) and
three-phase voltage sensing is applied to the DECS-100. Figure 4-7 shows another PMG application but
with single-phase voltage sensing. Figure 4-8 shows an application where DECS-100 operating power is
derived from the generator output (shunt application) and three-phase voltage sensing is applied to the
DECS-100. Figure 4-9 shows another shunt application but with single-phase sensing. Figure 4-10 shows
a DECS-100 powered by single-phase station power in a three-phase sensing application.
Figure 4-11 shows a typical connection diagram for two paralleled generators operating in cross-current
compensation (reactive differential) mode. The resistors shown have a value of 0.1 ohms. This is a typical
value that can be used to set the burden. (Ensure that the resistor power rating is adequate for the
installation.) The following paragraphs describe the mounting and wiring requirements for a CE (European
Community) compliant installation.
Mounting
The DECS-100 must be mounted inside a grounded, metal enclosure (conduit box). An access panel
should cover the opening for the front panel display.
Wiring
Wiring connected to the terminals listed below must be shielded. Each shield should be terminated to
ground on the outside of the conduit box.
? Current sensing terminals CT1 and CT2
? Relay output terminals AL1 and AL2
? Var/Power Factor control contact input terminals 52J and 52K
? Parallel generator compensation terminals 52L and 52M
? Raise and lower contact input terminals 6U, 6D, and 7
? Accessory input voltage terminals A and B
? Voltage matching contact input terminals VM and VMC 1. Tag and disconnect all wiring to the DECS-100. Be sure to insulate the wire terminals to prevent a
short circuit.
2. Start the prime mover and perform all engine governor adjustments.
3. After all initial governor adjustments have been made, shut down the prime mover.