UCD224A102通道模塊
5701系列控制系統(tǒng)用于提供以下操作:以及全面維護(hù)天然氣系統(tǒng)所需的工程設(shè)施檢測(cè)設(shè)備。
機(jī)架系統(tǒng)內(nèi)的每個(gè)控制卡顯示傳感器讀數(shù)、報(bào)警該信道的狀態(tài)和條件。
可以收集更多信息,并根據(jù)安全性狀態(tài),某些設(shè)置可以通過(guò)工程進(jìn)行調(diào)整安裝在機(jī)架上的卡。
系統(tǒng)的繼電器輸出配置為提供以下范圍:
輸出報(bào)警功能如下:
a、 故障報(bào)警當(dāng)在控制卡中檢測(cè)到故障時(shí),故障報(bào)警激活并且不是用戶可配置的。此外故障指示燈將點(diǎn)亮。
b、 抑制報(bào)警當(dāng)系統(tǒng)報(bào)警被禁止時(shí),禁止報(bào)警激活:任何原因,并且不可由用戶配置。此外,禁止LED將被照亮。c、 A1、A2和A3級(jí)報(bào)警當(dāng)氣體液位下降時(shí),A1、A2和A3液位報(bào)警激活被測(cè)量超過(guò)預(yù)配置的報(bào)警閾值。此外相關(guān)LED將點(diǎn)亮。
d、 STEL報(bào)警(短期暴露極限)當(dāng)時(shí)間加權(quán)平均值有毒氣體的濃度,通常平均超過(guò)10、15或30分鐘,超過(guò)預(yù)先配置的閾值。激活時(shí),STEL將:顯示在控制卡的信息顯示屏上。確切地繼電器卡和配置,期間關(guān)聯(lián)的報(bào)警LEDSTEL報(bào)警的設(shè)置將點(diǎn)亮,例如LTEL報(bào)警(長(zhǎng)期暴露極限)。當(dāng)時(shí)間加權(quán)平均值有毒氣體的濃度,通常平均超過(guò)8小時(shí)預(yù)先配置的閾值。激活時(shí),LTEL將顯示在控制卡的消息顯示。對(duì)于某些中繼卡和配置,設(shè)置期間與LTEL相關(guān)的報(bào)警LED警報(bào)將點(diǎn)亮。
速率報(bào)警(僅限2Vx軟件版本)
速率報(bào)警通過(guò)監(jiān)測(cè)
傳感器信號(hào)的上升速率,并提供早期報(bào)警指示
在傳感器信號(hào)達(dá)到下一級(jí)報(bào)警設(shè)定點(diǎn)之前。
g、 單獨(dú)報(bào)警
單個(gè)報(bào)警由單個(gè)控制器的輸入引起
信道超過(guò)預(yù)先配置的閾值,與任何
另一個(gè)控制信道。相關(guān)LED(A1、A2、A3、故障、禁止)將
報(bào)警狀態(tài)下控制卡上亮起。
INTRODUCTION
The 5701 Series Control System is equipped to provide the operational
and engineering facilities necessary to fully maintain a system of gas
detection equipment.
Each control card within a rack system displays a sensor reading, alarm
status and condition of that channel.
Further information can be gathered and, depending on the security
status, certain settings can be adjusted by means of an Engineering
Card fitted to the rack.
The relay outputs of the system are configured to provide a range of
output alarm functions as follows:
a. Fault Alarm
The fault alarm activates when a fault is detected in the control card
or associated sensor and is not user configurable. In addition the
FAULT LED will be illuminated.
b. Inhibit Alarm
The inhibit alarm activates when the system alarms are inhibited for
any reason and is not user configurable. In addition the INHIBIT LED
will be illuminated.
c. A1, A2 and A3 Level Alarms
The A1, A2 and A3 level alarms are activated when the level of gas
being measured crosses the preconfigured alarm threshold. In addition
the relevant LED will be illuminated.
d. STEL Alarm (Short Term Exposure Limit)
The STEL alarm will be activated when the time weighted average
concentration of a toxic gas, usually averaged over 10, 15 or 30
minutes, crosses a preconfigured threshold. When active STEL will
be shown on the message display of the control card. For certain
relay cards and configurations, the alarm LED associated during
setup to the STEL alarm will be illuminated.e. LTEL Alarm (Long Term Exposure Limit).
The LTEL alarm will be activated when the time weighted average
concentration of a toxic gas, usually averaged over 8 hours, crosses
a preconfigured threshold. When active LTEL will be shown on the
message display of the control card. For certain relay cards and
configurations, the alarm LED associated during setup to the LTEL
alarm will be illuminated.
f. Rate Alarm (Version 2Vx Software only)
The rate alarm predicts the future gas concentration by monitoring the
rate of rise of the sensor signal and provides an early alarm indication
before the sensor signal reaches the next level alarm set point.
g. Individual Alarm
An individual alarm is caused by the input to an individual control
channel crossing a preconfigured threshold and is not related to any
other control channel. The relevant LED (A1, A2, A3, Fault, Inhibit) will
illuminate on the control card with the alarm condition.