The HSS module provides control of throttle valve position in a
turbine speed control system. The MFP module sends data to
the HSS module, which directs the control of a hydraulic actu
ator (via a servo valve or I/H converter). By sending a position
demand to the HSS module, the MFP module initiates a change
in turbine speed. The position demand travels over the I/O
expander bus to the HSS module. An on-board microprocessor
reads the demand and loads it into a digital-to-analog (D/A)
converter. The resulting analog value drives the servo valve.
The servo valve loads hydraulic fluid to one side of a double
acting hydraulic actuator. As the hydraulic actuator opens or
closes the throttle valve, the turbine speed changes. If the
hydraulic actuator is being driven by an I/H converter, then
the HSS module scales the signal sent by the MFP module to a
four to 20 milliamp signal or 20 to 160 milliamp signal and the
PID controller circuitry is bypassed. This four to 20 milliamp
signal linearly drives the I/H converter to load hydraulic fluid
to one side of the double acting actuator.
The MFP module requires function code 55 or 150 in its config
uration to direct the operation of the IMHSS03 module. Func
tion code 55 defines the module address, mode of operation
(calibration or normal), calibration cycle time and stores cali
bration data. The ten output blocks include actuator position,
digital-to-analog converter output, servo valve coil output cur
rent, and status outputs for the module and process
equipment.