可以啟用或禁用線路冗余監(jiān)控。默認設(shè)置為禁用。啟用通過CI854/CI854A設(shè)置中的參數(shù)“線路冗余”完成。如果啟用了線路冗余,則在發(fā)生故障的情況下,特定線路將顯示警告“PROFIBUS上無活動”,例如PROFIBUS電纜上有故障。請啟用線路冗余監(jiān)控,如果使用了符合PNO冗余規(guī)范的冗余從設(shè)備和/或非冗余從設(shè)備提供了線路冗余接口和/或只有一個PROFIBUS接口的非冗余從機通過RLM01連接到CI854/CI854A。線路冗余的啟用不會影響CI854/CIL854A上LED RxA和RxB的指示。
The monitoring of the line redundancy can be enabled or disabled. The default is
disabled. The enabling is done via the parameter "Line redundancy" in the settings for CI854/CI854A. If the line redundancy is enabled the warning "No activity on
PROFIBUS" will be indicated for the specific line in the case of a failure, for
example if there is a fault on the PROFIBUS cable.
Please enable the monitoring of line redundancy, if
– redundant slaves according to the PNO redundancy specification are used
and/or
– non-redundant slaves provide a line redundant interface and/or
– non-redundant slaves with only one PROFIBUS interface are connected to
the CI854/CI854A with a RLM01 The enabling of line redundancy does not affect the indication of the LEDs RxA
and RxB on CI854/CI854A.