3BHE029110R0111控制器模塊
輸入電源(端子P1和P2):通電前連接,請參閱發(fā)電機隨附的接線圖。
按如下方式連接輸入電源。
-當穩(wěn)壓器設計為120 Vac±10%輸入功率時,以及65 Vdc最大連續(xù)輸出,連接單相120 Vac
端子P1和P2的電源。建議使用上述負載隔離和電壓匹配變壓器。
-當調節(jié)器設計用于240 V ac±10%輸入功率時,以及125 Vdc最大連續(xù)輸出,連接單相240 Vac端子P1和P2的電源。建議使用上述負載隔離和電壓匹配變壓器。
-當調節(jié)系統(tǒng)配有電磁閥時干擾? 濾波器,按接線圖所示連接與發(fā)電機組一起提供。
輸出功率(端子F+和F-):確保調節(jié)器輸出匹配發(fā)電機勵磁機額定值。KCR 760電壓調節(jié)器設計用于:120 Vac輸入設計用于65 Vdc最大連續(xù)輸出。這個KCR 760電壓調節(jié)器設計用于240 Vac輸入,設計用于:125 Vdc最大連續(xù)輸出。
保持調節(jié)器輸出和勵磁機之間的正確極埃爾德。
確保? 65 Vdc調節(jié)器的eld電阻不小于6.5和? 125 Vdc調節(jié)器的eld電阻不小于12.5。
確保? eld電路未接地和/或開路或短路發(fā)電機組運行期間。
因為穩(wěn)壓器輸出引線未連接到除勵磁機外的系統(tǒng)? 埃爾德,他們不是? 過濾。減少傳導EMI應使導線盡可能短并屏蔽。
通過將兩根引線穿過0.5一英寸導管。一般情況下,未屏蔽的距離不得超過1至2英尺屬于? eld領先。如果發(fā)電機內安裝了電壓調節(jié)器出線盒,可以在短時間內獲得滿意的結果非屏蔽導線。
接地:良好的電源接地不一定是良好的地面電磁干擾。使接地導線盡可能短最好是寬度為長度的1/5的銅帶。將機箱接地使所有接地共用。
Input power (terminal P1 and P2): Before making electrical connections, refer to the wiring diagram provided with the generator. Connect input power as follows. - When the regulator is designed for 120 Vac ±10% input power and 65 Vdc maximum continuous output, connect single-phase 120 Vac power to terminals P1 and P2. Refer above for recommended use of load isolation and voltage matching transformers. - When the regulator is designed for 240 V ac ±10% input power and 125 Vdc maximum continuous output, connect single-phase 240 Vac power to terminals P1 and P2. Refer above for recommended use of load isolation and voltage matching transformers. - When the regulating system is supplied with electromagnetic interference ? lters, connect as shown on the wiring diagram provided with the generator set. Output power (terminals F+ and F-): Be sure regulator output matches the generator exciter rating. The KCR 760 voltage regulator designed for 120 Vac input is designed for 65 Vdc maximum continuous output. The KCR 760 voltage regulator designed for 240 Vac input is designed for 125 Vdc maximum continuous output. Maintain correct polarity between the regulator output and exciter ? eld. Make sure ? eld resistance for the 65 Vdc regulator is not less than 6.5 and ? eld resistance for the 125 Vdc regulator is not less than 12.5 . Make sure the ? eld circuit is not grounded and/or opened or shorted during operation of the generator set. Because the regulator output leads are not connected to any part of the system except the exciter ? eld, they are not ? ltered. To minimize conducted EMI the keep the leads as short as possible and shielded. Effective shielding can be attained by routing both leads through 0.5 inch conduit. In general, do not leave unshielded more than 1 to 2 feet of ? eld leads. If the voltage regulator is installed within the generator outlet box, it is possible to achieve satisfactory results with short unshielded leads. Grounding: A good electrical power ground is not necessarily a good electromagnetic interference ground. Make the ground leads as short as possible, preferably of copper strap with a width of 1/5 the length. Grounding the chassis to earth ground makes all grounds common.