3BHE028959R0101數(shù)控模塊
高電壓!高漏電流!生命危險(xiǎn)、人身傷害危險(xiǎn)電擊!
? 在接通電氣裝置電源之前,所有外殼和電機(jī)必須永久接地
根據(jù)連接圖。這適用于即使是短暫的測(cè)試。
? 漏電流超過3.5mA。因此電氣設(shè)備和裝置必須始終牢固連接到供電網(wǎng)絡(luò)。
? 使用至少10 mm2交叉的銅導(dǎo)線該保護(hù)的整個(gè)過程的截面聯(lián)系
? 在啟動(dòng)之前,即使是短暫的測(cè)試,始終連接保護(hù)導(dǎo)體或接地線。
外殼上可能會(huì)出現(xiàn)高電壓水平可能導(dǎo)致嚴(yán)重電擊和人身傷害損傷
歐洲國家:EN 50178/1998,第5.3.2.1節(jié)。美國:參見國家電氣規(guī)范(NEC),國家
電氣制造商協(xié)會(huì)(NEMA)和當(dāng)?shù)亟ㄖ?guī)范。該設(shè)備的用戶必須維護(hù):
隨時(shí)遵守上述說明。保護(hù)性低電壓(PELV)保護(hù)電擊
電壓在5至50伏之間的所有連接和端子INDRAMAT產(chǎn)品為保護(hù)性低壓產(chǎn)品,其設(shè)計(jì)符合
接觸安全標(biāo)準(zhǔn)如下:
?國際:IEC 364-4-411.1.5
?歐盟國家:見EN 50178/1998,第5.2.8.1節(jié)。警告
錯(cuò)誤導(dǎo)致的高電壓連接!嚴(yán)重電氣危險(xiǎn),危及生命電擊和嚴(yán)重身體傷害!
? 僅設(shè)備、電氣部件和電纜保護(hù)性低壓型(PELV=保護(hù)型超低電壓)0至50伏的端子和夾具。
? 僅安全隔離電壓和電路可以連接。實(shí)現(xiàn)安全隔離,用于例如,使用隔離變壓器、光電耦合器或電池操作時(shí)。
High electrical voltage! High leakage current!
Danger to life, danger of injury and bodily harm
from electrical shock!
? Before switching on power for electrical units, all
housings and motors must be permanently grounded
according to the connection diagram. This applies
even for brief tests.
? Leakage current exceeds 3.5 mA. Therefore the
electrical equipment and units must always be firmly
connected to the supply network.
? Use a copper conductor with at least 10 mm2 cross
section over its entire course for this protective
connection!
? Prior to startups, even for brief tests, always connect
the protective conductor or connect with ground wire.
High voltage levels can occur on the housing that
could lead to severe electrical shock and personal
injury.
European countries: EN 50178/1998, section 5.3.2.1.
USA: See National Electrical Codes (NEC), National
Electrical Manufacturers Association (NEMA), and local
building codes. The user of this equipment must maintain
the above noted instructions at all times. Protection by protective low voltage (PELV) against
electrical shock
All connections and terminals with voltages between 5 and 50 Volts on
INDRAMAT products are protective low voltages designed in accordance
with the following standards on contact safety:
? International: IEC 364-4-411.1.5
? EU countries: see EN 50178/1998, section 5.2.8.1.
WARNING
High electrical voltage due to wrong
connections! Danger to life, severe electrical
shock and severe bodily injury!
? Only equipment, electrical components and cables of
the protective low voltage type (PELV = Protective
Extra Low Voltage) may be connected to all
terminals and clamps with 0 to 50 Volts.
? Only safely isolated voltages and electrical circuits
may be connected. Safe isolation is achieved, for
example, with an isolating transformer, an optoelectronic coupler or when battery-operated.