3BHE037864R0106庫存卡件
在禁止條件下,通道卡將繼續(xù)讀取
但是,氣體傳感器讀數(shù)在發(fā)生以下情況時(shí)不采取任何措施:超過報(bào)警條件。
A1-紅色LED
A1 LED指示預(yù)設(shè)的一級(jí)氣體報(bào)警已啟動(dòng)超過。如果出現(xiàn)故障或抑制處于活躍狀態(tài)。
d、 A2-紅色LED
A2 LED指示預(yù)設(shè)的二級(jí)氣體報(bào)警具有:已超過。在以下情況下,此警報(bào)將不起作用:故障或抑制條件激活。
A3-紅色LED
A3 LED指示預(yù)設(shè)的第三級(jí)氣體報(bào)警已啟動(dòng)超過。如果出現(xiàn)故障或抑制處于活躍狀態(tài)。復(fù)位/選擇按鈕
前面板復(fù)位/選擇按鈕提供四種功能:根據(jù)其操作方式:
a、 報(bào)警復(fù)位
復(fù)位/選擇按鈕在瞬間按下時(shí)復(fù)位
任何鎖定報(bào)警、非激活報(bào)警、故障、警告或信息消息,清除顯示峰值讀數(shù)指示器,并將
如果存在此類情況,則確認(rèn)更新。
注:“非活動(dòng)報(bào)警”描述了報(bào)警條件出現(xiàn)的情況
已清除,但由于已鎖定,報(bào)警仍指示信息對(duì)于非鎖定設(shè)置,指示的報(bào)警將清除報(bào)警條件清除時(shí)自動(dòng)。
b、 頻道選擇
按下復(fù)位/選擇按鈕約1.5秒,選擇控制卡,用于從工程卡。
c、 延長復(fù)位連續(xù)按下復(fù)位/選擇按鈕五秒鐘:
i、 清除通道最大和最小氣體讀數(shù)。
二,。重置任何有效的短期(STEL)和長期(LTEL)
曝光警報(bào)將定時(shí)器清零。
iii.對(duì)于激活的延時(shí)功能,激活任何具有即將觸發(fā)并清除任何保持的繼電器。
頻道取消選擇
復(fù)位/選擇按鈕,當(dāng)在如果選擇了控制卡,則從工程卡功能。
注意:也可以通過按鍵取消選擇控制卡
During the inhibit condition, the channel card will continue to read the
gas sensor reading, however, no action is taken in the event of an
alarm condition being exceeded.
c. A1 - Red LED
The A1 LED indicates that the preset first level gas alarm has been
exceeded. This alarm will not function in the event of either a fault or
inhibit condition being active.
d. A2 - Red LED
The A2 LED indicates that the preset second level gas alarm has
been exceeded. This alarm will not function in the event of either a
fault or inhibit condition being active.
e. A3 - Red LED
The A3 LED indicates that the preset third level gas alarm has been
exceeded. This alarm will not function in the event of either a fault or
inhibit condition being active.Reset/Select Push-button
The front panel RESET/SELECT push-button provides four functions
depending upon how it is operated:
a. Alarm Reset
The RESET/SELECT push-button, when pressed momentarily, resets
any latched alarm, non active alarms, faults, warning or information
messages, clears the display peak reading indicator and will
acknowledge an update if such a condition is present.
Note: 'Non active alarms' describe the occasion where the alarm condition
has cleared but the alarm is still indicated due to latched
information. For non-latched setups the indicated alarms will clear
automatically when the alarm condition clears.
b. Channel Select
The RESET/SELECT push-button, when pressed for approximately
1.5 seconds, selects the control card for operations controlled from
the Engineering Card.
c. Extended Reset
The RESET/SELECT push-button, when pressed continuously for
five seconds:
i. Clears the channel maximum and minimum gas readings.
ii. Resets any active short term (STEL) and long term (LTEL)
exposure alarms clearing the timer to zero.
iii. For active time delay functions, activates any relay with
impending trigger and clears any relay being held.
d. Channel Deselect
The RESET/SELECT push-button, when pressed momentarily while
a control card is selected, deselects the control card from the
Engineering Card functions.
Note: The control card may also be deselected by pressing the key