3BHE023681R0102通道卡件
根據(jù)配置,主報(bào)警或表決報(bào)警可能不會(huì)給出單獨(dú)的報(bào)警輸出。
h、 分區(qū)報(bào)警*分區(qū)報(bào)警由任何控制通道的輸入引起,從指定區(qū)域中的傳感器,超過預(yù)先配置的閾值。這個(gè)控制裝置上的相關(guān)LED(A1、A2、A3、故障、禁止)將點(diǎn)亮帶有報(bào)警條件的卡以及指定的控制卡區(qū)域主卡(除非安裝了高完整性繼電器卡)。i、 主報(bào)警器*任何指定控件的輸入都會(huì)導(dǎo)致主報(bào)警單個(gè)機(jī)架內(nèi)的通道超過預(yù)先配置的閾值。這個(gè)控制裝置上的相關(guān)LED(A1、A2、A3、故障、禁止)將點(diǎn)亮帶有報(bào)警條件的卡以及指定的控制卡主卡(除非裝有高完整性中繼卡)。投票警告*
投票報(bào)警是由同時(shí)存在相同的預(yù)配置組內(nèi)多個(gè)控制信道上的報(bào)警。相關(guān)LED(A1、A2、A3、故障、禁止)將在帶有報(bào)警條件的控制卡以及控制卡指定的投票主卡(除非裝有高完整性中繼)。
投票補(bǔ)償(僅限2V6及以上版本軟件)可能為:通過選擇以下選項(xiàng)之一
應(yīng)用于表決報(bào)警輸出操作:
以下配置:
a、 沒有補(bǔ)償。
b、 故障被視為報(bào)警。
c、 故障和抑制被視為報(bào)警。
d、 故障時(shí)的投票數(shù)減少。
e、 故障和禁止時(shí)的投票數(shù)減少。
表決補(bǔ)償有助于確保傳感器發(fā)生故障(或禁止)不阻止表決報(bào)警輸出。
k、 更新報(bào)警(僅限2Vx軟件版本)
更新報(bào)警設(shè)施提供通用報(bào)警指示
無論何時(shí)發(fā)生新的報(bào)警,即使以前的報(bào)警條件
存在。更新報(bào)警可配置為在單個(gè)信道或分組報(bào)警。例如主控或分區(qū)。
更新警報(bào)在僅配置了的系統(tǒng)中特別有用主繼電器或組/區(qū)域繼電器,其與以下原因相比,報(bào)警不會(huì)導(dǎo)致進(jìn)一步的繼電器輸出:初始警報(bào)。
相關(guān)LED(A1、A2、A3、故障、禁止)將在具有第2.3節(jié)所述報(bào)警條件的控制卡。
當(dāng)繼電器用于信號(hào)更新報(bào)警時(shí),無其他報(bào)警或者消息必須被分配給它們。更新配置應(yīng)避免出現(xiàn)“禁止”消息。
上升警報(bào)
上升報(bào)警由以下參數(shù)的上升水平引起:
測(cè)量值超過預(yù)先配置的閾值,也將導(dǎo)致
相關(guān)報(bào)警LED點(diǎn)亮。
Depending upon the configuration, control cards configured for Zoned,
Master or Voted alarms may not give individual alarm outputs.
h. Zoned Alarm*
A zoned alarm is caused by the input to any control channel, from a
sensor in a designated area, crossing a preconfigured threshold. The
relevant LED (A1, A2, A3, Fault, Inhibit) will illuminate on the control
card with the alarm condition and also on the control card designated
the Zone Master Card (unless it is fitted with a High Integrity Relay
Card).
i. Master Alarm*
A master alarm is caused by the input to any designated control
channel within a single rack crossing a preconfigured threshold. The
relevant LED (A1, A2, A3, Fault, Inhibit) will illuminate on the control
card with the alarm condition and also on the control card designated
the Master Card (unless it is fitted with a High Integrity Relay Card).Voted Alarm*
A voted alarm is caused by the simultaneous presence of an identical
alarm on more than one control channel within a preconfigured group.
The relevant LED (A1, A2, A3, Fault, Inhibit) will illuminate on the
control cards with the alarm condition and also on the control card
designated the Vote Master Card (unless it is fitted with a High
Integrity Relay).
Vote compensation (Version 2V6 and above Software only) may be
applied to the voted alarm output operation by selecting one of the
following configurations:
a. No compensation.
b. Faults counted as alarms.
c. Faults and inhibits counted as alarms.
d. Vote count reduction on faults.
e. Vote count reduction on faults and inhibit.
Vote compensation is useful to ensure that sensors in fault (or
inhibit) do not prevent voted alarm outputs.
k. Update Alarm (Version 2Vx Software only)
The update alarm facility provides a common alarm indication
whenever a new alarm occurs, even if a previous alarm condition
exists. The update alarm can be configured to operate on a single
channel or on a grouped alarm. eg. master or zoned.
The update alarm is especially useful in systems configured with only
master or group/zone relays, where the occurrence of subsequent
alarms will not cause further relay output compared to that caused by
the initial alarm.
The relevant LED (A1, A2, A3, Fault, Inhibit) will illuminate on the
control card with the alarm condition as described in section 2.3.
When relays are used for signalling update alarms, no other alarms
or messages must be allocated to them. Configuration of update
messages for “inhibit” should be avoided.
l. Rising Alarm
A rising alarm is caused by a rising level of the parameter being
measured crossing a preconfigured threshold and will also cause the
associated alarm LED to illuminate.