ASPC2 LAN控制器維護(hù)以下計(jì)數(shù)器。它們都是1字節(jié)長(zhǎng)。什么時(shí)候這些計(jì)數(shù)器達(dá)到255,在清除之前保持在255。對(duì)于AOP,計(jì)數(shù)器名稱相同作為AOP標(biāo)記名。ErrInvReqLen計(jì)數(shù)器寄存器Local:Slot:S.Data[19]的低位字節(jié)(位0-7)統(tǒng)計(jì)無效的請(qǐng)求長(zhǎng)度錯(cuò)誤。當(dāng)掃描儀軟件向LAN控制器發(fā)送的消息太長(zhǎng)的這是一個(gè)內(nèi)部錯(cuò)誤,不應(yīng)發(fā)生。ErrFifo計(jì)數(shù)器

GVC703AE01集成控制卡件寄存器Local:Slot:S.Data[19]的高位字節(jié)8-15統(tǒng)計(jì)FIFO溢出錯(cuò)誤。這些當(dāng)LAN控制器無法足夠快地寫入內(nèi)存時(shí),會(huì)發(fā)生錯(cuò)誤。這是一個(gè)內(nèi)部錯(cuò)誤,不應(yīng)發(fā)生。ERRRXOVERRUN計(jì)數(shù)器寄存器Local:Slot:S.Data[20]的低位字節(jié),位0-7,統(tǒng)計(jì)接收溢出錯(cuò)誤。這是一個(gè)內(nèi)部錯(cuò)誤,不應(yīng)發(fā)生。ErrDblTok計(jì)數(shù)器寄存器Local:Slot:S.Data[20]的高位字節(jié)8-15統(tǒng)計(jì)雙令牌錯(cuò)誤。這些當(dāng)多個(gè)節(jié)點(diǎn)認(rèn)為自己擁有令牌或存在連接錯(cuò)誤時(shí),可能會(huì)發(fā)生錯(cuò)誤,復(fù)制節(jié)點(diǎn),等等。掃描儀撤回到“不持有令牌”狀態(tài)(決定沒有令牌),并等待直到再次將令牌傳遞給它。ErrRespErr計(jì)數(shù)器
寄存器Local:Slot:S.Data[21]的低位字節(jié)為0-7,用于統(tǒng)計(jì)消息發(fā)送時(shí)的響應(yīng)錯(cuò)誤失敗或目標(biāo)沒有響應(yīng)。此錯(cuò)誤可能是由于硬件損壞或故障裝電線。
ErrSyniErr計(jì)數(shù)器寄存器Local:Slot:S.Data[21]的高位字節(jié)8-15表示一般網(wǎng)絡(luò)錯(cuò)誤。這些錯(cuò)誤發(fā)生在網(wǎng)絡(luò)出現(xiàn)問題時(shí),但在您建立網(wǎng)絡(luò)之前超時(shí)錯(cuò)誤。
ASPC2 PROFIBUS Controller Statistics
The ASPC2 LAN controller maintains the following counters. They are all 1 byte long. When
these counters reach 255, they hold at 255 until cleared. For AOP, the counter name is the same
as the AOP tag name.
The ErrInvReqLen Counter
The low byte of register Local:Slot:S.Data[19], bits 0-7, counts invalid request length errors.
These errors occur when the scanner software gives the LAN controller a message that is too
long. This is an internal error and should never occur.
The ErrFifo Counter
The high byte of register Local:Slot:S.Data[19], bits 8-15, counts FIFO overflow errors. These
errors occur when the LAN controller cannot write to memory fast enough. This is an internal
error and should never occur.
The ErrRxOverun Counter
The low byte of register Local:Slot:S.Data[20], bits 0-7, counts receive overrun errors. This is an
internal error and should never occur.
The ErrDblTok Counter
The high byte of register Local:Slot:S.Data[20], bits 8-15, counts double token errors. These
errors may occur when more than one node thinks it has the token or there are wiring errors,
duplicate nodes, and so on. The scanner withdraws to the “not hold token” state (decides it
doesn't have the token) and waits until it gets the token passed to it again.
The ErrRespErr Counter
The low byte of register Local:Slot:S.Data[21], bits 0-7, counts response errors when a message
fails or there is no response from the destination. This error may be due to bad hardware or faulty
wiring.
The ErrSyniErr Counter
The high byte of register Local:Slot:S.Data[21], bits 8-15, indicates general network errors.
These errors occur when there are problems on the network, but before you get a network
timeout error.