HESG324426R0001控制器,HESG324426R0001配置手冊
1.1.1掃描儀功能SST-PB3-CLX-RLL是用于1756(ControlLogix)背板和霍尼韋爾PlantScape系統(tǒng)。它支持CLX處理器和PROFIBUS網(wǎng)絡(luò)上的DP遠(yuǎn)程輸入/輸出設(shè)備,用作PROFIBUS DP遠(yuǎn)程輸入/輸出掃描儀。
信息技術(shù):
?DP主設(shè)備和從設(shè)備經(jīng)過認(rèn)證(帶有Profibus固件版本7.25)
?最多支持15個僅偵聽連接和1個輸出連接
?作為主機,支持同步和凍結(jié)命令
?支持羅克韋爾的RSLogix 5000附加配置文件(AOP)
?最多可掃描125個從機

HESG324426R0001控制器?支持和掃描每個從機最多122個字的輸入數(shù)據(jù)和122個字的輸出數(shù)據(jù)
?可以駐留在本地或遠(yuǎn)程CLX機箱中的任何插槽中。最多可以有8個掃描儀在機架中。
?支持所有標(biāo)準(zhǔn)PROFIBUS波特率(9600、19200、31.25k、45.45k、93.75k、,187.5k、500k、1.5M、3M、6M、12M)
?支持以下DPV1主服務(wù):
?1級:MSAC1\u讀,MSAC2\u寫
?2級:MSAC2\u啟動、MSAC2\u讀取、MSAC2\u寫入、MSAC2\u空閑、,MSAC2\u中止
?最多可同時處理16個1級和16個2級命令
?使用DPV1時,最多可以處理16個2級連接(到16個2級DPV1從機)僅限2類通信
?可作為DPV0從機
?允許同時操作PROFIBUS主設(shè)備和從設(shè)備(高達(dá)12M)
?作為主機,最多支持1984字節(jié)的輸入數(shù)據(jù)和1968字節(jié)的輸出4個輸入/輸出頁面中的數(shù)據(jù)
?作為主機,支持多達(dá)256個輸入/輸出模塊的配置
1.1.1 Scanner Capabilities
The SST-PB3-CLX-RLL is the PROFIBUS scanner for the 1756 (ControlLogix) backplane and
Honeywell PlantScape system. It enables communication between a CLX processor and
DP remote I/O devices on a PROFIBUS network, acting as a PROFIBUS DP remote I/O
scanner. It:
?
DP Master and Slave Certified (with Profibus Firmware Revision 7.25)
?
Supports up to 15 listen-only connections plus 1 output connection
?
As a Master supports Sync and Freeze commands
?
Supports Rockwell’s RSLogix 5000 Add-on-Profile (AOP)
?
Can scan up to 125 slaves
?
Supports and scans up to 122 words of input data and 122 words of output data per slave
?
Can reside in any slot in the local or remote CLX chassis. You can have up to 8 scanners
in a rack.
?
Supports all standard PROFIBUS baud rates (9600, 19200, 31.25k, 45.45k, 93.75k,
187.5k, 500k, 1.5M, 3M, 6M, 12M)
?
Supports the following DPV1 Master services:
?
Class 1: MSAC1_Read, MSAC2_Write
?
Class 2: MSAC2_Initiate, MSAC2_Read, MSAC2_Write, MSAC2_Idle,
MSAC2_Abort
?
Can handle up to 16 Class 1 and 16 Class 2 commands simultaneously
?
Can handle up to 16 Class 2 connections (to 16 Class 2 DPV1 Slaves) when using DPV1
Class 2 Communication only
?
Can act as a DPV0 slave
?
Allows for simultaneous operation of PROFIBUS Master and Slave (up to 12M)
?
As a Master, supports a maximum of 1984 bytes of input data and 1968 bytes of output
data with in 4 I/O pages
?
As a Master, supports configurations with up to 256 I/O modules